Kit Aquapump Retrofit Tronic, GTF1600-S1, level sensor
Type of wastewater: wastewater without sewage
Installation situation: installation in on-site collecting tank
Version:
Type of system: Single station
Shut-off valve: yes
Pump control: Control unit
Backflow preventer: integrated
Delivery state: Modular set for assembly on site
General characteristics:
Standard: EN 12050-2
Tank:
Pressure pipe connection: horizontal
Pressure pipe connection (DN): 50 mm
Pressure pipe connection (OD): 63 mm
Pumping device:
Pump: GTF 1600
Number of pumps: 1
Max. pumping capacity: 49 m3/h
Max. pumping height: 9.3 m
Operating voltage: 400 V
Mains frequency: 50 Hz
Operating mode: S1
Power P1: 1.6 kW
Power P2: 1.2 kW
Speed: 2,900 U/min
Type of fuse required (electrical protection): C 16 A
Max. temperature (permanent) of conveyed material: 40 °C
Connection type: coded plug
Weight: 12 kg
Impeller type: Multi-vane impeller
Length of mains cable for pump: 10 m
Rated current: 2.9 A
Protection class (pump): IP 68 (3m)
Protection class: I
Type of pump connection cable: H07RN-F 7G 1.5 mm2
Temperature monitoring: integrated
Control:
Control unit: Comfort
Operating voltage: 400 V
Mains frequency: 50 Hz
Self-diagnosis system (SDS): yes
Battery buffering: yes
Multi-line display: yes
Log book function: yes
USB interface: yes
GSM interface: yes
Potential-free contact: optional
Type of fuse required (electrical protection): 3 x C 16 A
Protection class control unit: IP 54
Type of level measurement: hydrostatic
Level measurement instrument: Level sensor
Alarm sensor: Level sensor